Home Products Voltronic UPS
10 to 20 kVA in a 250 x 826 x 630 mm tower, available three-phase in and out, three-phase in with single-phase out, or single to single — the unit for a site whose supply arrangement is not settled.
Battery type 12V/9Ah Communication interface RS232/USB Current crest ratio 3:1 Dimension (mm) 250 x 630 x 826 Eco mode efficiency (%) 98.5 Harmonic distortion (%) 2-5 Humidity (%) 95 Max charging current (A) 1
All specifications 28 AC Phase 3P/3P, 3P/1P or 1P/1P (selectable) AC voltage regulation batt mode 1 Input frequency range (Hz) 46-54 or 56-64 Output frequency range (Hz) 50 ± 0.1 or 60 ± 0.1 Output voltage (V) 380/400/415 or 220/230/240 Power factor 1.0 Synchronized frequency range (Hz) 46-54 or 56-64
Battery Battery type 12V/9Ah Max charging current (A) 1
Protection Overload capacity 100-110%: 60 min; 110-125%: 10 min; 125-150%: 1 min; >150%: immediate
Communication Communication interface RS232/USB
General Device class UPS Current crest ratio 3:1 Dimension (mm) 250 x 630 x 826 Eco mode efficiency (%) 98.5 Harmonic distortion (%) 2-5 Humidity (%) 95 Input voltage range (V) 190-520 @ 50% load; 305-478 @ 100% load Noise (dB) 62-65 Nominal input voltage (V) 380/400/415 or 220/230/240 Operating temperature (°C) 0 to 40 Package dimension (mm) 250 x 630 x 826 Package weight (kg) 25-133 Safety standard EN 62040-1:2008/A1:2013, IEC 62040-1:2008/A1:2013, CE Low Voltage Directive, EN 62040-2:2006 (C3), CE EMC Directive Snmp support Optional Transfer time (ms) 0 Waveform Pure sine wave Weight (kg) 25-133