The 6 kVA build, for a rack of network gear or a small server stack.
| Device class | UPS |
|---|---|
| Phase | Single-Phase |
| Rated power (kVA) | 6 |
| Rated power (kW) | 5.4 |
| AC mode efficiency (%) | 95 |
| Battery type | LiFePO4 |
| Charging voltage (V) | 210 |
| Communication interface | USB |
| Device class | UPS |
|---|---|
| Nominal battery voltage (V) | 192 |
| Phase | Single-Phase |
| Rated power (kVA) | 6 |
| Rated power (kW) | 5.4 |
| AC mode efficiency (%) | 95 |
| AC voltage regulation batt mode | 1 |
| Battery mode efficiency (%) | 93 |
| Battery type | LiFePO4 |
| Charging voltage (V) | 210 |
| Communication interface | USB |
| Current crest ratio | 3:1 |
| Dimension (mm) | 438 x 520 x 44 |
| Harmonic distortion (%) | 2-4 |
| Humidity (%) | 0-95 |
| Input frequency range (Hz) | 46-54 / 56-64 |
| Input voltage range (V) | 110-300 ± 3% @ 50% load; 176-300 ± 3% @ 100% load |
| Max charging current (A) | 6 |
| Noise (dB) | 55 |
| Nominal input voltage (V) | 208/220/230/240 |
| Operating temperature (°C) | 0 to 40 |
| Output frequency range (Hz) | 50 ± 0.1 or 60 ± 0.1 |
| Output voltage (V) | 208/220/230/240 |
| Overload capacity | ≤105%: warning only; 105-125%: 1 min; >125%: 1 s |
| Package dimension (mm) | 438 x 520 x 44 |
| Package weight (kg) | 9.8 |
| Power factor | 0.9 |
| Snmp support | Optional |
| Synchronized frequency range (Hz) | 46-54 or 56-64 |
| Transfer time (ms) | 0-4 |
| Waveform | Pure sine wave |
| Weight (kg) | 9.8 |